招考网【官方站】权威信息发布平台!

综采工作面供电设计(5)

时间:2012-08-28 20:36来源:未知 作者:86zhaokao.cn 点击:
o =0.247 / km, X o =0.075 / km R g1 =0.2470.24=0.05928 X g1 =0.0750.24=0.018 R=0.01824+0.041167+0.05928=0.118687 X=0.076418+0.0125+0.018=0.106918 4.破碎机电机处短路电流I d4 计算 MYP 335+11
o=0.247 / km, Xo=0.075 / km
Rg1=0.247×0.24=0.05928
Xg1=0.075×0.24=0.018
∑R=0.01824+0.041167+0.05928=0.118687
∑X=0.076418+0.0125+0.018=0.106918


4.破碎机电机处短路电流Id4计算
MYP  3×35+1×16型电缆的电阻、电抗:L2=10米,
阻抗参数:Ro=0.683 / km, Xo=0.084 / km
Rg1=0.683×0.01=0.00683
Xg1=0.084×0.01=0.00084
∑R=0.01824+0.041167+0.00683=0.066237
∑X=0.076418+0.0125+0.00084=0.089758


5.2#移变二次出口端的短路电流Id5计算
(1)系统阻抗
变压器二次电压1200V,容量500kVA,系统短路容量按50MVA计算;则系统电抗为

(2)高压电缆阻抗
10kV电缆L1=0.49km
查表得,Ro=0.588 / km, Xo=0.078 / km
高压电缆电阻、电抗:
Rg=0.588×0.49=0.28812
Xg=0.078×0.49=0.03822
(3)变压器阻抗
查表得KBSGZY-500/10型移动变电站的vs=4, ΔPN.T=3100W
则变压器的电阻、电抗:
0.017856
0.1152




6.1#馈电入口处短路电流Id6计算
MYP  3×70+1×25型电缆的电阻、电抗:L7=230米,
阻抗参数:Ro=0.346 / km, Xo=0.078 / km
Rg1=0.346×0.23=0.07958
Xg1=0.078×0.23=0.01794
∑R=0.022038+0.07958=0.101618 (责任编辑:86zhaokao.cn)
织梦二维码生成器
顶一下
(0)
0%
踩一下
(0)
0%
------分隔线----------------------------
发表评论
请自觉遵守互联网相关的政策法规,严禁发布色情、暴力、反动的言论。
评价:
表情:
用户名: 验证码:点击我更换图片
栏目列表
推荐内容